top of page

Safenames Commercial Solar PV Remediation

A 220 kWp system review following a significant electrical malfunction.

Investigation Findings

CEC investigated the 220 kWp installation following an electrical incident. The review identified issues with string design, MPPT allocation, shading, DC connections and cable management.

String design

Mismatched string lengths required review and redesign to suit the array layout and inverter inputs.

MPPT allocation

The review identified unsuitable allocation of strings to inverter MPPT inputs.

Shading

Shaded and unshaded roof areas were connected together, requiring the electrical layout to be reconsidered.

DC connections and cable management

DC terminations and cable routing required remedial work.

Redesign Solution and Implementation

CEC redesigned the DC layout, corrected string lengths and MPPT allocation, replaced DC terminations, and improved cable management and containment. The work addressed the electrical faults identified during the investigation. The Safenames project also included a ballast review that identified approximately eight tonnes of excess ballast.

Implementation Scope

The work covered electrical investigation, DC redesign, corrected string lengths and MPPT allocation, replacement terminations and improved cable management. Findings and remedial work were specific to this installation.

Discuss Your Commercial Solar System

Get help with an existing system